Electrical Cabinet Suppression

A complete fully automatic and pre-engineered suppression system

Electrical fire hazards are shockingly common. They’re responsible for 13% of non-home structure fires and they cannot be extinguished with water. To get a reliable protection from electrical fires, explore Honeywell’s Electrical Cabinet Suppression (ECS) System – a world-class offering from the world leader in fire safety solutions.

Causes of Fire

The same electricity we rely on can also cause of a lot of devastation in the form of fires. Some of the many causes of electrical fires are:

  • Short-circuits
  • Overloading or overheating of components
  • Defective electrical connections
  • Electrical malfunctioning
  • Electrical surges
  • Fatigue/end of life of electrical wires
  • Incorrect installation
  • Faulty equipment
image

Electrical Cabinet Suppression (ecs) System

Making electrical panels and cabinets fire-safe

Designed to protect electrical enclosures/circuitry, Honeywell’s comprehensive, pre-engineered ECS system reduces the risk of electrical fires, and prevents potential devastation to business and property. Not only does it protect business assets, it also prevents downtime and ensures business continuity. Perfect for ‘microenvironments’ where fire hazards are likely to be in the enclosed space, it leaves out no residue behind which eliminates the need for an extensive area clean up.

  • Minimises even the most critical electrical fire risks including short circuits, overloading, overheating, electrical surges, etc.
  • Full automatic operation – no human intervention required
  • Can be installed directly inside electrical cabinets, closer to where fires usually start
  • UL-listed clean agent and heat detection tube for quick fire suppression
  • Optional dual-valve outlet: reliable, affordable protection even for large-sized cabinets
  • Leaves no dirty residue or unpleasant odour
  • Environment-friendly operation
  • Available in 3 sizes from 2.5lbs to 10lbs
Download Brochure

Product Components

  • Cylinder With Fk-5-1-12 Agent

  • Heat Detection Tube

  • Pressure Switch

  • Master Control Unit

  • Dual Outlet Valve

Available in 3 Sizes

image

ECS-250/252

The ECS-250 and ECS-252 are Direct Low Pressure systems filled with 1.13 kg of non-toxic and odourless FK-5-1-12 fire suppression clean agent. The system operates at a working pressure of 195/240psi (13.5/16Bar) and a temperature range of -17.8° C to 54.4° C. It comes with an EOL adapter (with gauge) and cylinder valve Assy, 4 rubber grommets, 25 plastic loop clamps and a cylinder mounting bracket.

The assembly is installed on-site with the included bracket. The Heat detection tube is installed inside the electrical panel using the included rubber grommets and plastic loop clamps. The tube is pressurised with dry Nitrogen to 13.5/16 Bar using the Filling Adapter and connected to the cylinder valve assembly on-site. The EOL Adapter with gauge is connected at the end of the tube. The pressure gauge is kept outside the electrical panel for clear visibility and to ease inspection. The ball valve on the cylinder valve assembly is kept in the “ON” position to complete the installation and commissioning.

ECS-252 provides a dual valve outlet as against ECS-250 which has a single valve outlet port.

  • FK-5-1-12: 1.13 kg
  • Ozone Depletion Potential (ODP): 0
  • Global Warming Potential: 1
  • Atmospheric Lifetime: 5 days
  • SNAP: Yes
Download Brochure